Fuses

B300 - Fuse 1000V DC aBat DC 2xM12 1250A

Reference 678.183.99.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 1250
Applicable standards IEC
Power loss (W) 235
Rated Voltage Un DC (V) 1000
Time costant L/R (ms) 2
Series name B300
Rated breaking capacity I1 DC (kA) 100
Fixing dimensions M12
Melting I²t value (A²s) 537500
Minimum breaking current (A) 12500
Fuse Connection/Terminal type Screw fixing
Total clearing I²t @Un DC (A²s) 1620000
Product available on request Ask for more information

P103 - Fuse 550V DC EV with pins 10 AMP

Reference 679.360.73.0.0 - Manufacturer FAULTRAP
Rated current In (A) 10
Applicable standards IEC
Power loss (W) 1,97
Rated Voltage Un DC (V) 550
Time costant L/R (ms) 2
Series name P103
Rated breaking capacity I1 DC (kA) 20000
Fuse Dimension (mm) 10x38
Melting I²t value (A²s) 7
Voltage of total clearing I2t test 550
Total clearing I²t @Un AC (A²s) 40
Product available on request Ask for more information

B100 - Fuse 1000VDC aBat 630A - 132,7mm - Silver Plated

Reference 679.983.97.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 630
Applicable standards IEC, UL
Power loss (W) 120
Rated Voltage Un DC (V) 1000
Time costant L/R (ms) 2
Series name B100
Rated breaking capacity I1 DC (kA) 100000
Fuse Dimension (mm) 63,5x167
Melting I²t value (A²s) 108000
Minimum breaking current (A) 6300
Fuse Connection/Terminal type Screw fixing
Voltage of total clearing I2t test 1000
Total clearing I²t @Un AC (A²s) 324000
Product available on request Ask for more information

V108 - Fuse 10x85 1500VDC gPV UL 10A

Reference 685.060.16.0.0 - Manufacturer FAULTRAP
Class gPV
Rated current In (A) 10
Applicable standards IEC, UL
Power loss (W) 2,99
Rated Voltage Un DC (V) 1500
Series name V108
Rated breaking capacity I1 DC (kA) 20000
Fuse Dimension (mm) 10x85
Melting I²t value (A²s) 12,7
Fuse Connection/Terminal type Cylindrical
Voltage of total clearing I2t test 1500
Total clearing I²t @Un AC (A²s) 102
Weight (gr) 12
Price List €10.81/pc
Quantity

RL12 - Fuse 25x60mm 125VDC 25A

Reference 685.348.33.0.0 - Manufacturer FAULTRAP
Rated current In (A) 25
Power loss (W) 3,5
Rated Voltage Un DC (V) 125
Time costant L/R (ms) 3
Series name RL12
Rated breaking capacity I1 DC (kA) 10000
Melting I²t value (A²s) 35
Total clearing I²t @Un AC (A²s) 240
Price List €3.62/pc
Quantity

20PV22 - Fuse 2000VDC gPV 22x85 inline 15A 6/8 AWG

Reference 689.656.50.0.0 - Manufacturer FAULTRAP
Class gPV
Rated current In (A) 15
Applicable standards IEC
Power loss (W) 4.8
Rated Voltage Un DC (V) 2000
Time costant L/R (ms) 1-3
Series name 20PV22
Rated breaking capacity I1 DC (kA) 50
Fuse Dimension (mm) 22x85
Melting I²t value (A²s) 38
Fuse Connection/Terminal type In-line for copper cable
Product available on request Ask for more information

20PV3 - Fuse 2000VDC gPV 76x269mm axial terminals 225mm 350A

Reference 693.162.36.0.0 - Manufacturer FAULTRAP
Class gPV
Rated current In (A) 350
Applicable standards IEC
Power loss (W) 81
Rated Voltage Un DC (V) 2000
Time costant L/R (ms) 1-3
Series name 20PV3
Rated breaking capacity I1 DC (kA) 50
Fuse Dimension (mm) 76x269
Melting I²t value (A²s) 73750
Minimum breaking current (A) 700
Fuse Connection/Terminal type Screw fixing
Product available on request Ask for more information

PV22 - Fuse 22x65mm 1500VDC gPV UL 30A

Reference 693.945.08.0.0 - Manufacturer FAULTRAP
Class gPV
Rated current In (A) 30
Applicable standards UL
Power loss (W) 7
Rated Voltage Un DC (V) 1500
Time costant L/R (ms) 3
Series name PV22
Rated breaking capacity I1 DC (kA) 10000
Fuse Dimension (mm) 22x65
Melting I²t value (A²s) 230
Fuse Connection/Terminal type Cylindrical
Voltage of total clearing I2t test 1500
Total clearing I²t @Un AC (A²s) 1800
Product available on request Ask for more information

B300 - Fuse 1000V DC aBat DC 2xM12 1000A

Reference 695.363.75.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 1000
Applicable standards IEC
Power loss (W) 200
Rated Voltage Un DC (V) 1000
Time costant L/R (ms) 2
Series name B300
Rated breaking capacity I1 DC (kA) 100
Fuse Dimension (mm) 86x106
Fixing dimensions M12
Melting I²t value (A²s) 267000
Minimum breaking current (A) 10000
Fuse Connection/Terminal type Screw fixing
Total clearing I²t @Un DC (A²s) 801000
Product available on request Ask for more information

NR2A - Fuse DIN000 80mm aR 700VDC/690VAC with ind. lug 180A

Reference 696.362.07.0.0 - Manufacturer FAULTRAP
Class aR
Rated current In (A) 180
Rated Voltage Un AC (V) 690
Dimension 000
Applicable standards IEC
Power loss (W) 42.5
Rated Voltage Un DC (V) 700
Time costant L/R (ms) 2
Series name NR2A
Rated breaking capacity I1 DC (kA) 30000
Melting I²t value (A²s) 4120
Fuse Connection/Terminal type Screw fixing
Fixing connection centres (mm) 80
Voltage of total clearing I2t test 700
Total clearing I²t @Un AC (A²s) 15100
Rated breaking capacity I1 AC (kA) 200000
Product available on request Ask for more information

B500 - Fuse 1500VDC aBat 2xM12 with micro adapter 1800A

Reference 697.280.78.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 1800
Applicable standards IEC
Power loss (W) 430
Rated Voltage Un DC (V) 1500
Time costant L/R (ms) 3
Series name B500
Rated breaking capacity I1 DC (kA) 250000
Fuse Dimension (mm) 103x144
Fixing dimensions M12
Melting I²t value (A²s) 1615000
Minimum breaking current (A) 19800
Fuse Connection/Terminal type Screw fixing
Voltage of total clearing I2t test 1500
Total clearing I²t @Un AC (A²s) 8720000
Product available on request Ask for more information

B200 - Fuse 38x73mm 1000VDC BS aBat 125A

Reference 698.861.52.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 125
Applicable standards IEC
Power loss (W) 21
Rated Voltage Un DC (V) 1000
Time costant L/R (ms) 2
Series name B200
Rated breaking capacity I1 DC (kA) 50000
Fuse Dimension (mm) 38x73
Melting I²t value (A²s) 3400
Fuse Connection/Terminal type Screw fixing
Voltage of total clearing I2t test 1000
Total clearing I²t @Un AC (A²s) 13000
Product available on request Ask for more information

X100 - Fuse 22x65mm 1000VAC gG 8A

Reference 699.108.71.0.0 - Manufacturer FAULTRAP
Class gG
Rated current In (A) 8
Rated Voltage Un AC (V) 1000
Applicable standards IEC
Power loss (W) 1,9
Series name X100
Fuse Dimension (mm) 22x65
Melting I²t value (A²s) 241
Fuse Connection/Terminal type Cylindrical
Total clearing I²t @Un AC (A²s) 8500
Rated breaking capacity I1 AC (kA) 50
Product available on request Ask for more information
Class aR
Rated current In (A) 900
Rated Voltage Un AC (V) 690
Dimension SQB2
Applicable standards IEC
Power loss (W) 105
Series name C200
Fixing dimensions M10
Melting I²t value (A²s) 170000
Fuse Connection/Terminal type Screw fixing
Total clearing I²t @Un AC (A²s) 1173000
Rated breaking capacity I1 AC (kA) 200
Product available on request Ask for more information

20PV22 - Fuse 2000VDC gPV 22x85 32A

Reference 684.844.13.0.0 - Manufacturer FAULTRAP
Class gPV
Rated current In (A) 32
Applicable standards IEC
Power loss (W) 9,7
Rated Voltage Un DC (V) 2000
Time costant L/R (ms) 1-3
Series name 20PV22
Rated breaking capacity I1 DC (kA) 50
Fuse Dimension (mm) 22x85
Melting I²t value (A²s) 225
Fuse Connection/Terminal type Cylindrical
Product available on request Ask for more information

BSDC - Fuse 38x73mm 1000VDC BS aBat 250A

Reference 631.812.67.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 250
Applicable standards IEC
Power loss (W) 39
Rated Voltage Un DC (V) 1000
Time costant L/R (ms) 2
Series name BSDC
Rated breaking capacity I1 DC (kA) 50
Fuse Dimension (mm) 38x127
Melting I²t value (A²s) 21000
Fuse Connection/Terminal type Screw fixing
Fixing connection centres (mm) 99
Total clearing I²t @Un AC (A²s) 79800
Product available on request Ask for more information

L108 - In-Line Rugged 10x85 Fuse + Holder 1500VDC 12A

Reference 631.813.48.0.0 - Manufacturer FAULTRAP
Class gPV
Rated current In (A) 12
Applicable standards IEC
Power loss (W) 3,2
Rated Voltage Un DC (V) 1500
Series name L108
Rated breaking capacity I1 DC (kA) 20000
Fuse Dimension (mm) 10x85
Melting I²t value (A²s) 16,3
Fuse Connection/Terminal type Cylindrical
Voltage of total clearing I2t test 1500
Total clearing I²t @Un AC (A²s) 177
Product available on request Ask for more information

NRAB - Fuse 690V AC aR NH00 with indicator 250A

Reference 633.071.01.0.0 - Manufacturer FAULTRAP
Class aR
Rated current In (A) 250
Rated Voltage Un AC (V) 690
Dimension NH00
Applicable standards IEC
Power loss (W) 57
Series name NRAB
Melting I²t value (A²s) 10150
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 770
Total clearing I²t @Un AC (A²s) 49500
Rated breaking capacity I1 AC (kA) 200000
Product available on request Ask for more information
Filter by
Manufacturer
Series name
Fuse size
Class
Fuse Connection/Terminal type
Rated current In (A)
Rated Voltage Un AC (V)
Rated Voltage Un DC (V)
Applicable standards
Product added to compare.