Fuse 12kV 87x292 back-up striker no temp.lim200ARC125
Fuse 12kV 87x292 back-up striker no temp.lim200ARC125

Fuse 12kV 87x292 back-up striker no temp.lim200ARC125

Reference: 3002014.200LM.0  -  Manufacturer: SIBA
€514.96 /pc VAT excl.

Product Details

Class
HH Back up
Rated current In (A)
200
Rated Voltage Un AC (V)
6000
Applicable standards
IEC
Power loss (W)
71
Resistance (ohm)
0,0032
Fuse Dimension (mm)
85x292
Melting I²t value (A²s)
227000
Minimum breaking current (A)
870
Fuse Connection/Terminal type
Cylindrical
Voltage of total clearing I2t test
5220
Total clearing I²t @Un AC (A²s)
1300000
Rated breaking capacity I1 AC (kA)
80000