List of products by manufacturer FAULTRAP

B500 - Fuse 1500VDC aBat 2xM12 with micro adapter 700A

Reference 946.887.63.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 700
Voltage of total I2t test 1500
Format Screw fixing
Dimension 89x144mm
Pre-arcing I2t value (A2s) 208000
Total I2t value (A2s) 1169000
Homologations IEC
Power loss (W) 185
Rated Voltage Un DC (V) 1500
Rated break.capacity I1 DC (A) 100000
Time costant L/R (ms) 3
Min breaking current (A) 8000
Series name B100
Product available on request Ask for more information

EV65.1000 - Fuse 1000VDC 22x65 cylindrical 50A

Reference 968.836.79.0.0 - Manufacturer FAULTRAP
Class EV full
Rated current In (A) 50
Voltage of total I2t test 1000
Format Cylindrical
Dimension 22x65mm
Pre-arcing I2t value (A2s) 685
Total I2t value (A2s) 2800
Homologations UL
Power loss (W) 11
Rated Voltage Un DC (V) 1000
Rated break.capacity I1 DC (A) 25000
Time costant L/R (ms) 2,5
Series name EV65
Product available on request Ask for more information

AB22 - Fuse 22x65 1000VDC aBat 40A

Reference 972.091.49.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 60
Rated Voltage Un AC (V) 1000
Format Cylindrical
Dimension 22x65mm
Pre-arcing I2t value (A2s) 1270
Total I2t value (A2s) 7000
Homologations IEC
Power loss (W) 0
Rated Voltage Un DC (V) 1000
Rated break.capacity I1 DC (A) 10000
Series name AB22
Product available on request Ask for more information

NRAB - Fuse 690V AC aR NH00 with indicator 63A

Reference 444.949.61.0.0 - Manufacturer FAULTRAP
Class aR
Rated current In (A) 63
Rated Voltage Un AC (V) 690
Rated break.capacity I1 AC (A) 200000
Voltage of total I2t test 770
Format NH knife contact
Dimension NH00
Pre-arcing I2t value (A2s) 520
Total I2t value (A2s) 2500
Homologations IEC
Power loss (W) 9,5
Rated Voltage Un DC (V) 700
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 2
Series name NRAB
Product available on request Ask for more information

B100 - Fuse 1000VDC aBat 750A - 152,7mm - Silver Plated

Reference 456.954.32.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 750
Voltage of total I2t test 1000
Format Screw fixing
Dimension 63,5x130,5mm
Pre-arcing I2t value (A2s) 166000
Total I2t value (A2s) 500000
Power loss (W) 140
Rated Voltage Un DC (V) 1000
Rated break.capacity I1 DC (A) 100000
Time costant L/R (ms) 2
Series name B100
Min breaking current (A) 7500
Product available on request Ask for more information

B100 - Fuse 1000VDC aBat 900A - 152,7mm - Silver Plated

Reference 456.383.65.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 900
Voltage of total I2t test 1000
Format Screw fixing
Dimension 63,5x203,2mm
Pre-arcing I2t value (A2s) 267000
Total I2t value (A2s) 813000
Power loss (W) 170
Rated Voltage Un DC (V) 1000
Rated break.capacity I1 DC (A) 100000
Time costant L/R (ms) 2
Series name B100
Min breaking current (A) 9000
Product available on request Ask for more information

T500 - Fuse 500VDC aBat d:38mm axial 80mm 80A

Reference 449.701.36.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 80
Voltage of total I2t test 500
Format Screw fixing
Dimension 38x80mm
Pre-arcing I2t value (A2s) 1300
Total I2t value (A2s) 2000
Power loss (W) 7,5
Rated Voltage Un DC (V) 500
Rated break.capacity I1 DC (A) 100000
Time costant L/R (ms) 2
Series name T500
Product available on request Ask for more information

B100 - Fuse 1000VDC aBat double body 1600A - Silver Plated

Reference 407.568.47.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 1600
Voltage of total I2t test 1000
Format Screw fixing
Pre-arcing I2t value (A2s) 740000
Total I2t value (A2s) 2200000
Power loss (W) 315
Fuses dimension 63,5x130,5
Rated Voltage Un DC (V) 1000
Rated break.capacity I1 DC (A) 100000
Time costant L/R (ms) 2
Series name B100
Min breaking current (A) 16000
Product available on request Ask for more information

B100 - Fuse 1000VDC aBat 900A - 132,7mm - Silver Plated

Reference 374.004.92.0.0 - Manufacturer FAULTRAP
Class aBat
Rated current In (A) 900
Voltage of total I2t test 1000
Format Screw fixing
Pre-arcing I2t value (A2s) 267000
Total I2t value (A2s) 813000
Power loss (W) 170
Fuses dimension 63,5x167
Rated Voltage Un DC (V) 1000
Rated break.capacity I1 DC (A) 100000
Time costant L/R (ms) 2
Series name B100
Min breaking current (A) 9000
Product available on request Ask for more information

NRAB - Fuse 690V AC aR NH00 with indicator 40A

Reference 383.177.16.0.0 - Manufacturer FAULTRAP
Class aR
Rated current In (A) 40
Rated Voltage Un AC (V) 690
Rated break.capacity I1 AC (A) 200000
Voltage of total I2t test 770
Format NH knife contact
Dimension NH00
Pre-arcing I2t value (A2s) 230
Total I2t value (A2s) 1100
Homologations IEC
Power loss (W) 7,2
Rated Voltage Un DC (V) 700
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 2
Series name NRAB
Product available on request Ask for more information
Product added to compare.