All Products

Fuse NH0S aM 500V double indicator 200A

Reference 383180.0.0 - Manufacturer DF
Class aM
Rated current In (A) 200
Rated Voltage Un AC (V) 500
Dimension NH0S
Applicable standards IEC
Melting I²t value (A²s) 92000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 690
Total clearing I²t @Un AC (A²s) 320000
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 270
Price List €12.38/pc
Quantity

Fuse NH1 aM 500V double indicator 224A

Reference 383265.0.0 - Manufacturer DF
Class aM
Rated current In (A) 224
Rated Voltage Un AC (V) 500
Dimension NH1
Applicable standards IEC
Power loss (W) 14,6
Melting I²t value (A²s) 240000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 529312
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 470
Price List €14.61/pc
Quantity

Fuse NH1 aM 500V double indicator 250A

Reference 383270.0.0 - Manufacturer DF
Class aM
Rated current In (A) 250
Rated Voltage Un AC (V) 500
Dimension NH1
Applicable standards IEC
Power loss (W) 18,1
Melting I²t value (A²s) 291000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 641790
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 470
Price List €14.71/pc
Quantity

Fuse NH2 aM 500V double indicator 400A

Reference 383380.0.0 - Manufacturer DF
Class aM
Rated current In (A) 400
Rated Voltage Un AC (V) 500
Dimension NH2
Applicable standards IEC
Power loss (W) 27,8
Melting I²t value (A²s) 502000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 1308183
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 710
Price List €22.47/pc
Quantity

Fuse NH3 aM 500V double indicator 630A

Reference 383470.0.0 - Manufacturer DF
Class aM
Rated current In (A) 630
Rated Voltage Un AC (V) 500
Dimension NH3
Applicable standards IEC
Power loss (W) 45,9
Melting I²t value (A²s) 1373000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 3360000
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 1200
Price List €45.93/pc
Quantity

Fuse NH4 screw fixing aM 500V double indicator 315A

Reference 383505.0.0 - Manufacturer DF
Class aM
Rated current In (A) 315
Rated Voltage Un AC (V) 500
Dimension NH4
Applicable standards IEC
Power loss (W) 18,8
Melting I²t value (A²s) 463000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 1021130
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 2250
Price List €108.83/pc
Quantity

Fuse NH4 screw fixing aM 500V double indicator 400A

Reference 383510.0.0 - Manufacturer DF
Class aM
Rated current In (A) 400
Rated Voltage Un AC (V) 500
Dimension NH4
Applicable standards IEC
Power loss (W) 23,5
Melting I²t value (A²s) 502000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 1308183
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 2250
Price List €110.57/pc
Quantity

Fuse NH4 screw fixing aM 500V double indicator 500A

Reference 383515.0.0 - Manufacturer DF
Class aM
Rated current In (A) 500
Rated Voltage Un AC (V) 500
Dimension NH4
Applicable standards IEC
Power loss (W) 34
Melting I²t value (A²s) 760000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 1980516
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 2250
Price List €111.74/pc
Quantity

Fuse NH4 screw fixing aM 500V double indicator 630A

Reference 383520.0.0 - Manufacturer DF
Class aM
Rated current In (A) 630
Rated Voltage Un AC (V) 500
Dimension NH4
Applicable standards IEC
Power loss (W) 49
Melting I²t value (A²s) 1423000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 3708255
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 2250
Price List €112.62/pc
Quantity

Fuse NH4 screw fixing aM 500V double indicator 800A

Reference 383525.0.0 - Manufacturer DF
Class aM
Rated current In (A) 800
Rated Voltage Un AC (V) 500
Dimension NH4
Applicable standards IEC
Power loss (W) 52
Melting I²t value (A²s) 1880000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 4567527
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 2250
Price List €116.13/pc
Quantity

Fuse NH4 screw fixing aM 500V double indicator 1000A

Reference 383530.0.0 - Manufacturer DF
Class aM
Rated current In (A) 1000
Rated Voltage Un AC (V) 500
Dimension NH4
Applicable standards IEC
Power loss (W) 80
Melting I²t value (A²s) 4500000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 11282902
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 2250
Price List €118.94/pc
Quantity

Fuse NH4 screw fixing aM 500V double indicator 1250A

Reference 383535.0.0 - Manufacturer DF
Class aM
Rated current In (A) 1250
Rated Voltage Un AC (V) 500
Dimension NH4
Applicable standards IEC
Power loss (W) 108
Melting I²t value (A²s) 7000000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 17607924
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 2250
Price List €149.24/pc
Quantity

EV65.1500 - Fuse 1500VDC 22x65 cylindrical 60A

Reference 384.236.42.0.0 - Manufacturer FAULTRAP
Class EV full
Rated current In (A) 60
Applicable standards UL
Power loss (W) 12
Rated Voltage Un DC (V) 1500
Time costant L/R (ms) 2,5
Series name EV65.1500
Rated breaking capacity I1 DC (kA) 25000
Fuse Dimension (mm) 22x65
Melting I²t value (A²s) 1220
Fuse Connection/Terminal type Cylindrical
Voltage of total clearing I2t test 1500
Total clearing I²t @Un AC (A²s) 7500
Product available on request Ask for more information

UR22 - Fuse 690V AC 22x58 cylindrical 50A

Reference 384.770.34.0.0 - Manufacturer FAULTRAP
Class aR
Rated current In (A) 50
Rated Voltage Un AC (V) 550
Applicable standards IEC, UL
Power loss (W) 13,3
Series name UR22
Melting I²t value (A²s) 195
Fuse Connection/Terminal type Cylindrical
Total clearing I²t @Un AC (A²s) 955
Rated breaking capacity I1 AC (kA) 200
Product available on request Ask for more information
Filter by
Manufacturer
Series name
Class
Rated Voltage Un AC (V)
Rated Voltage Un DC (V)
Rated insultaion voltage AC (V)
Rated insulated voltage DC (V)
Applicable standards
Product added to compare.
Product added to wishlist