Fuse 400V NH000 gG 20A

Reference 2026113.20.0 - Manufacturer SIBA
Class gG
Rated current In (A) 20
Rated Voltage Un AC (V) 400
Rated break.capacity I1 AC (A) 120000
Voltage of total I2t test 440
Format NH knife contact
Dimension NH000
Pre-arcing I2t value (A2s) 690
Total I2t value (A2s) 1550
Homologations IEC
Power loss (W) 2,2
Price List €20.43/pc
Quantity

Fuse 400V NH000 gG 25A

Reference 2026113.25.0 - Manufacturer SIBA
Class gG
Rated current In (A) 25
Rated Voltage Un AC (V) 400
Rated break.capacity I1 AC (A) 120000
Voltage of total I2t test 440
Format NH knife contact
Dimension NH000
Pre-arcing I2t value (A2s) 1400
Total I2t value (A2s) 3000
Homologations IEC
Power loss (W) 2,3
Price List €20.43/pc
Quantity

Fuse 400V NH000 gG 35A

Reference 2026113.35.0 - Manufacturer SIBA
Class gG
Rated current In (A) 35
Rated Voltage Un AC (V) 400
Rated break.capacity I1 AC (A) 120000
Voltage of total I2t test 440
Format NH knife contact
Dimension NH000
Pre-arcing I2t value (A2s) 3450
Total I2t value (A2s) 7750
Homologations IEC
Power loss (W) 3,3
Price List €20.44/pc
Quantity

Fuse 400V NH000 gG 40A

Reference 2026113.40.0 - Manufacturer SIBA
Class gG
Rated current In (A) 40
Rated Voltage Un AC (V) 400
Rated break.capacity I1 AC (A) 120000
Voltage of total I2t test 440
Format NH knife contact
Dimension NH000
Pre-arcing I2t value (A2s) 5600
Total I2t value (A2s) 11500
Homologations IEC
Power loss (W) 3,5
Price List €20.44/pc
Quantity

Fuse 400V NH000 gG 50A

Reference 2026113.50.0 - Manufacturer SIBA
Class gG
Rated current In (A) 50
Rated Voltage Un AC (V) 400
Rated break.capacity I1 AC (A) 120000
Voltage of total I2t test 440
Format NH knife contact
Dimension NH000
Pre-arcing I2t value (A2s) 6450
Total I2t value (A2s) 18000
Homologations IEC
Power loss (W) 3,9
Price List €20.44/pc
Quantity

Fuse 400V NH000 gG 6A

Reference 2026113.6.0 - Manufacturer SIBA
Class gG
Rated current In (A) 6
Rated Voltage Un AC (V) 400
Rated break.capacity I1 AC (A) 120000
Voltage of total I2t test 440
Format NH knife contact
Dimension NH000
Pre-arcing I2t value (A2s) 70
Total I2t value (A2s) 240
Homologations IEC
Power loss (W) 1,9
Price List €62.95/pc
Quantity

Fuse 400V NH000 gG 63A

Reference 2026113.63.0 - Manufacturer SIBA
Class gG
Rated current In (A) 63
Rated Voltage Un AC (V) 400
Rated break.capacity I1 AC (A) 120000
Voltage of total I2t test 440
Format NH knife contact
Dimension NH000
Pre-arcing I2t value (A2s) 9950
Total I2t value (A2s) 32000
Homologations IEC
Power loss (W) 4,2
Price List €4.81/pc
Quantity

Fuse 400V NH000 gG 80A

Reference 2026113.80.0 - Manufacturer SIBA
Class gG
Rated current In (A) 80
Rated Voltage Un AC (V) 400
Rated break.capacity I1 AC (A) 120000
Voltage of total I2t test 440
Format NH knife contact
Dimension NH000
Pre-arcing I2t value (A2s) 15500
Total I2t value (A2s) 47500
Homologations IEC
Power loss (W) 5,1
Price List €4.81/pc
Quantity

Fuse SQB2 110mmgRL/gS 690VAC/500VDC lat switch adapt 90 160A

Reference 2027834.160.0 - Manufacturer SIBA
Rated current In (A) 160
Rated Voltage Un AC (V) 690
Rated break.capacity I1 AC (A) 200000
Voltage of total I2t test 690
Format Screw fixing
Dimension SQB2-110mm
Pre-arcing I2t value (A2s) 7400
Total I2t value (A2s) 47000
Homologations IEC
Power loss (W) 23
Rated Voltage Un DC (V) 500
Rated break.capacity I1 DC (A) 32000
Time costant L/R (ms) 15
Product available on request Ask for more information

Fuse SQB2 110mmgRL/gS 690VAC/500VDC lat switch adapt 90 200A

Reference 2027834.200.0 - Manufacturer SIBA
Rated current In (A) 200
Rated Voltage Un AC (V) 690
Rated break.capacity I1 AC (A) 200000
Voltage of total I2t test 690
Format Screw fixing
Dimension SQB2-110mm
Pre-arcing I2t value (A2s) 15000
Total I2t value (A2s) 95000
Homologations IEC
Power loss (W) 27
Rated Voltage Un DC (V) 500
Rated break.capacity I1 DC (A) 32000
Product available on request Ask for more information

Fuse SQB2 110mmgRL/gS 690VAC/500VDC lat switch adapt 90 250A

Reference 2027834.250.0 - Manufacturer SIBA
Rated current In (A) 250
Rated Voltage Un AC (V) 690
Rated break.capacity I1 AC (A) 200000
Voltage of total I2t test 690
Format Screw fixing
Dimension SQB2-110mm
Pre-arcing I2t value (A2s) 30000
Total I2t value (A2s) 190000
Homologations IEC
Power loss (W) 30
Rated Voltage Un DC (V) 500
Rated break.capacity I1 DC (A) 32000
Product available on request Ask for more information