Fuse NH1XL 1100V DC gRL NH1XL screw fixing with ind. 200A

Reference 2002934.200.0 - Manufacturer SIBA
Class gRL, gS
Rated current In (A) 200
Applicable standards IEC, UL
Power loss (W) 38
Rated Voltage Un DC (V) 1100
Time costant L/R (ms) 10
Melting I²t value (A²s) 19200
Voltage of total clearing I2t test 100000
Total clearing I²t @Un AC (A²s) 126000
Rated breaking capacity I1 AC (kA) 100000
Price List €898.35/pc
Quantity

Fuse NH1 gG 500V with striker 125A

Reference 2000913.125.0 - Manufacturer SIBA
Class aM
Rated current In (A) 125
Rated Voltage Un AC (V) 500
Dimension NH1
Applicable standards IEC
Power loss (W) 10
Melting I²t value (A²s) 44400
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 440
Total clearing I²t @Un AC (A²s) 127500
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 410
Price List €209.60/pc
Quantity

Fuse NH00 gG 500V with striker 20A

Reference 2000713.20.0 - Manufacturer SIBA
Class aM
Rated current In (A) 20
Rated Voltage Un AC (V) 500
Dimension NH00
Applicable standards IEC
Power loss (W) 2,4
Melting I²t value (A²s) 760
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 440
Total clearing I²t @Un AC (A²s) 1480
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 190
Price List €39.62/pc
Quantity

Fuse NH00 gR/aR 500V with striker 63A

Reference 2000704.63.0 - Manufacturer SIBA
Class gR
Rated current In (A) 63
Rated Voltage Un AC (V) 500
Dimension NH00
Applicable standards IEC
Power loss (W) 14
Melting I²t value (A²s) 330
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 2600
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 190
Price List €54.14/pc
Quantity

Fuse NH00 gG 500V with striker 25A

Reference 2000713.25.0 - Manufacturer SIBA
Class aM
Rated current In (A) 25
Rated Voltage Un AC (V) 500
Dimension NH00
Applicable standards IEC
Power loss (W) 2,3
Melting I²t value (A²s) 1440
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 440
Total clearing I²t @Un AC (A²s) 2890
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 190
Price List €39.54/pc
Quantity

Fuse NH00 gG 500V with striker 32A

Reference 2000713.32.0 - Manufacturer SIBA
Class aM
Rated current In (A) 32
Rated Voltage Un AC (V) 500
Dimension NH00
Applicable standards IEC
Power loss (W) 3,1
Melting I²t value (A²s) 2600
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 400
Total clearing I²t @Un AC (A²s) 5630
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 190
Price List €39.59/pc
Quantity

Fuse NH1 aR 500V with striker 200A

Reference 2000904.200.0 - Manufacturer SIBA
Class aR
Rated current In (A) 200
Rated Voltage Un AC (V) 500
Dimension NH1
Applicable standards IEC
Power loss (W) 40
Melting I²t value (A²s) 5800
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 37000
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 410
Price List €59.95/pc
Quantity

Fuse NH1 aR 500V with striker 63A

Reference 2000904.63.0 - Manufacturer SIBA
Class aR
Rated current In (A) 63
Rated Voltage Un AC (V) 500
Dimension NH1
Applicable standards IEC
Power loss (W) 18
Melting I²t value (A²s) 330
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 2600
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 410
Price List €120.98/pc
Quantity

Fuse NH1 aR 500V with striker 125A

Reference 2000904.125.0 - Manufacturer SIBA
Class aR
Rated current In (A) 125
Rated Voltage Un AC (V) 500
Applicable standards IEC
Power loss (W) 33
Melting I²t value (A²s) 1660
Fuse Connection/Terminal type NH knife contact
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 12300
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 410
Price List €122.10/pc
Quantity

Fuse NH1 aR 500V with striker 160A

Reference 2000904.160.0 - Manufacturer SIBA
Class aR
Rated current In (A) 160
Rated Voltage Un AC (V) 500
Dimension NH1
Applicable standards IEC
Power loss (W) 40
Melting I²t value (A²s) 2400
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 19500
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 410
Price List €54.78/pc
Quantity

Fuse NH1 aR 500V with striker 80A

Reference 2000904.80.0 - Manufacturer SIBA
Class aR
Rated current In (A) 80
Rated Voltage Un AC (V) 500
Dimension NH1
Applicable standards IEC
Power loss (W) 22
Melting I²t value (A²s) 510
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 4200
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 410
Price List €121.19/pc
Quantity

Fuse NH1 aR 500V with striker 224A

Reference 2000904.224.0 - Manufacturer SIBA
Class aR
Rated current In (A) 224
Rated Voltage Un AC (V) 500
Dimension NH1
Applicable standards IEC
Power loss (W) 53
Melting I²t value (A²s) 7600
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 500
Total clearing I²t @Un AC (A²s) 42000
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 410
Price List €155.85/pc
Quantity
Product added to compare.