All Products

Fuse 1500VDC NH3L gPV UL248-19 with indicator 400A

Reference 2024329.400.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 400
Voltage of total I2t test 1500
Weight (g) 2080
Format NH knife contact
Dimension NH3L
Pre-arcing I2t value (A2s) 106000
Total I2t value (A2s) 534000
Power loss (W) 64
Voltage drop (mV) 64
Rated Voltage Un DC (V) 1500
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 3
Price List €444.35/pc
Quantity

Fuse NH3L gR 1000VDC 125A

Reference 2003120.125.0 - Manufacturer SIBA
Class gR
Rated current In (A) 125
Rated Voltage Un AC (V) 900
Rated break.capacity I1 AC (A) 30000
Voltage of total I2t test 1100
Weight (g) 1380
Dimension NH3L
Pre-arcing I2t value (A2s) 3300
Total I2t value (A2s) 24000
Homologations IEC
Power loss (W) 27
Rated Voltage Un DC (V) 1000
Rated break.capacity I1 DC (A) 30000
Price List €164.60/pc
Quantity

Fuse NH3L gR 1000VDC 125A

Reference 2003120.125.0 - Manufacturer SIBA
Class gR
Rated current In (A) 125
Rated break.capacity I1 AC (A) 30000
Voltage of total I2t test 1100
Weight (g) 1380
Format NH knife contact
Dimension NH3L
Pre-arcing I2t value (A2s) 3300
Total I2t value (A2s) 24000
Homologations IEC
Power loss (W) 27
Rated Voltage Un DC (V) 1000
Rated break.capacity I1 DC (A) 30000
Price List €223.22/pc
Quantity

Fuse SQB1 screw M8 gPV 1100VDC 160A

Reference 2001928.160.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 160
Voltage of total I2t test 1100
Format Screw fixing
Dimension SQB1 screw M8
Pre-arcing I2t value (A2s) 7600
Total I2t value (A2s) 25000
Homologations IEC
Power loss (W) 36
Rated Voltage Un DC (V) 1100
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 3
Product available on request Ask for more information

Fuse NH1XL 1500DC gPV UL 2579 with indicator 70A

Reference 2004129.70.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 70
Voltage of total I2t test 1500
Weight (g) 800
Dimension NH1XL
Voltage drop (mV) 1
Rated Voltage Un DC (V) 1500
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 3
Price List €230.18/pc
Quantity

Fuse NH1XL 1500DC gPV UL 2579 with indicator 80A

Reference 2004129.80.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 80
Voltage of total I2t test 1500
Weight (g) 800
Dimension NH1XL
Pre-arcing I2t value (A2s) 1060
Total I2t value (A2s) 5300
Power loss (W) 24
Rated Voltage Un DC (V) 1500
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 3
Price List €208.16/pc
Quantity

Fuse NH1XL 1500DC gPV UL 2579 with indicator 70A

Reference 2004129.70.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 70
Voltage of total I2t test 1500
Weight (g) 800
Format NH knife contact
Dimension NH1XL
Voltage drop (mV) 1
Rated Voltage Un DC (V) 1500
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 3
Price List €230.18/pc
Quantity

Fuse NH1XL 1500DC gPV UL 2579 with indicator 80A

Reference 2004129.80.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 80
Voltage of total I2t test 1500
Weight (g) 800
Format NH knife contact
Dimension NH1XL
Pre-arcing I2t value (A2s) 1060
Total I2t value (A2s) 6400
Power loss (W) 24
Rated Voltage Un DC (V) 1500
Rated break.capacity I1 DC (A) 100000
Time costant L/R (ms) 3
Price List €277.54/pc
Quantity

Fuse 1500VDC NH3L gPV UL248-19 without indicator 250A

Reference 2024328.250.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 250
Voltage of total I2t test 1500
Weight (g) 2060
Dimension NH3L
Pre-arcing I2t value (A2s) 32000
Total I2t value (A2s) 160000
Homologations IEC
Power loss (W) 43
Rated Voltage Un DC (V) 1500
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 3
Product available on request Ask for more information

Fuse 1500VDC NH3L gPV UL248-19 without indicator 250A

Reference 2024328.250.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 250
Voltage of total I2t test 1500
Weight (g) 2060
Format NH knife contact
Dimension NH3L
Pre-arcing I2t value (A2s) 32000
Total I2t value (A2s) 160000
Homologations IEC
Power loss (W) 43
Rated Voltage Un DC (V) 1500
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 3
Price List €1,424.31/pc
Quantity

Fuse NH1 1000VDC gPV top indicator UL 248-19 200A

Reference 2055629.200.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 200
Voltage of total I2t test 1000
Weight (g) 466
Dimension NH1
Pre-arcing I2t value (A2s) 9900
Total I2t value (A2s) 30300
Power loss (W) 32
Rated Voltage Un DC (V) 1000
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 2
Price List €32.01/pc
Quantity

Fuse NH1 1000VDC gPV top indicator UL 248-19 200A

Reference 2055629.200.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 200
Voltage of total I2t test 1000
Weight (g) 466
Format NH knife contact
Dimension NH1
Pre-arcing I2t value (A2s) 9900
Total I2t value (A2s) 30300
Power loss (W) 32
Rated Voltage Un DC (V) 1000
Rated break.capacity I1 DC (A) 30000
Time costant L/R (ms) 2
Price List €45.09/pc
Quantity
Filter by
Manufacturer
Class
Rated Voltage Un AC (V)
Series name
more... less
Rated Voltage Un DC (V)
Rated insultaion voltage AC (V)
Rated insulated voltage DC (V)
Fuses format
Fuses dimension
Inside diameter (mm)
Distance (mm)
Homologations
Product added to compare.