Fuse NH3L 900VDC gRL 350A

Reference 2003134.350.0 - Manufacturer SIBA
Class gRL, gS
Rated current In (A) 350
Dimension NH3L
Applicable standards IEC
Power loss (W) 52
Rated Voltage Un DC (V) 900
Rated breaking capacity I1 DC (kA) 50000
Melting I²t value (A²s) 79700
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 1100
Total clearing I²t @Un AC (A²s) 438000
Weight (gr) 1370
Price List €147.33/pc
Quantity

Fuse NH3L 900VDC gRL 400A

Reference 2003134.400.0 - Manufacturer SIBA
Class gRL, gS
Rated current In (A) 400
Dimension NH3L
Applicable standards IEC
Power loss (W) 58
Rated Voltage Un DC (V) 900
Rated breaking capacity I1 DC (kA) 300000
Melting I²t value (A²s) 106000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 1100
Total clearing I²t @Un AC (A²s) 585000
Weight (gr) 2080
Price List €215.83/pc
Quantity

Fuse NH3L 900VDC gRL 450A

Reference 2003134.450.0 - Manufacturer SIBA
Class gRL, gS
Rated current In (A) 450
Dimension NH3L
Applicable standards IEC
Power loss (W) 62
Rated Voltage Un DC (V) 900
Rated breaking capacity I1 DC (kA) 50000
Melting I²t value (A²s) 153000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 900
Total clearing I²t @Un AC (A²s) 970000
Weight (gr) 2080
Price List €224.46/pc
Quantity

Fuse NH3L 900VDC gRL 500A

Reference 2003134.500.0 - Manufacturer SIBA
Class gRL, gS
Rated current In (A) 500
Dimension NH3L
Applicable standards IEC
Power loss (W) 74
Rated Voltage Un DC (V) 900
Rated breaking capacity I1 DC (kA) 50000
Melting I²t value (A²s) 189000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 900
Total clearing I²t @Un AC (A²s) 1200000
Price List €233.83/pc
Quantity

Fuse NH3L 900VDC gRL 550A

Reference 2003134.550.0 - Manufacturer SIBA
Class gRL, gS
Rated current In (A) 550
Dimension NH3L
Applicable standards IEC
Power loss (W) 79
Rated Voltage Un DC (V) 900
Rated breaking capacity I1 DC (kA) 50000
Melting I²t value (A²s) 258000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 900
Total clearing I²t @Un AC (A²s) 1640000
Price List €1,445.01/pc
Quantity

Fuse NH3L 900VDC gRL 630A

Reference 2003134.630.0 - Manufacturer SIBA
Class gRL, gS
Rated current In (A) 630
Dimension NH3L
Applicable standards IEC
Power loss (W) 90
Rated Voltage Un DC (V) 900
Rated breaking capacity I1 DC (kA) 50000
Melting I²t value (A²s) 331000
Fuse Connection/Terminal type NH knife
Voltage of total clearing I2t test 900
Total clearing I²t @Un AC (A²s) 2100000
Price List €1,625.88/pc
Quantity

Fuse NH4 gTF 500V 1000A

Reference 2003202.1000.0 - Manufacturer SIBA
Class gTF
Rated current In (A) 1000
Rated Voltage Un AC (V) 500
Dimension NH4
Power loss (W) 78
Melting I²t value (A²s) 5800000
Fuse Connection/Terminal type Screw fixing
Voltage of total clearing I2t test 440
Total clearing I²t @Un AC (A²s) 14400000
Rated breaking capacity I1 AC (kA) 120000
Weight (gr) 2300
Price List €1,898.01/pc
Quantity

Fuse SQB2 screw fixing gPV UL 2579 1100VDC 200A

Reference 2003428.200.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 200
Rated Voltage Un AC (V) 1100
Dimension SQB2
Applicable standards IEC, UL
Power loss (W) 39
Melting I²t value (A²s) 13000
Fuse Connection/Terminal type Screw fixing
Voltage of total clearing I2t test 1100
Total clearing I²t @Un AC (A²s) 63000
Rated breaking capacity I1 AC (kA) 30000
Weight (gr) 1380
Price List €311.14/pc
Quantity

Fuse SQB2 screw fixing gPV UL 2579 1100VDC 250A

Reference 2003428.250.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 250
Rated Voltage Un AC (V) 1100
Dimension SQB2
Applicable standards IEC, UL
Power loss (W) 42
Melting I²t value (A²s) 26500
Fuse Connection/Terminal type Screw fixing
Voltage of total clearing I2t test 1100
Total clearing I²t @Un AC (A²s) 130000
Rated breaking capacity I1 AC (kA) 30000
Weight (gr) 1380
Price List €331.89/pc
Quantity

Fuse SQB2 screw fixing gPV UL 2579 1100VDC 300A

Reference 2003428.300.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 300
Rated Voltage Un AC (V) 1100
Dimension SQB2
Applicable standards IEC, UL
Power loss (W) 56
Melting I²t value (A²s) 38000
Fuse Connection/Terminal type Screw fixing
Voltage of total clearing I2t test 1100
Total clearing I²t @Un AC (A²s) 185000
Rated breaking capacity I1 AC (kA) 30000
Weight (gr) 1380
Price List €1,514.33/pc
Quantity

Fuse SQB2 screw fixing gPV UL 2579 1100VDC 315A

Reference 2003428.315.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 315
Rated Voltage Un AC (V) 1100
Dimension SQB2
Applicable standards IEC, UL
Power loss (W) 59
Melting I²t value (A²s) 38000
Fuse Connection/Terminal type Screw fixing
Voltage of total clearing I2t test 1100
Total clearing I²t @Un AC (A²s) 185000
Rated breaking capacity I1 AC (kA) 30000
Weight (gr) 1380
Price List €356.07/pc
Quantity

Fuse SQB3 screw fixing gPV UL 2579 1100VDC 350A

Reference 2003428.350.0 - Manufacturer SIBA
Class gPV
Rated current In (A) 350
Rated Voltage Un AC (V) 1100
Dimension SQB2
Applicable standards IEC, UL
Power loss (W) 62
Melting I²t value (A²s) 57000
Fuse Connection/Terminal type Screw fixing
Voltage of total clearing I2t test 1100
Total clearing I²t @Un AC (A²s) 280000
Rated breaking capacity I1 AC (kA) 30000
Weight (gr) 1380
Price List €400.57/pc