VT protection

There are 294 products.
Showing 1 - 24 of 294 items
  • Fuse 12kV 53x442 back-up with striker 2A
    3010113.2.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 12000
    • Rated current In (A) 2
    • Pre-arcing I2t value (A2s) 3,2
    • Total I2t value (A2s) 9,8
    • Voltage of total I2t test 12000
    • Rated break.capacity I1 AC (A) 63000
    • Power loss (W) 8,2
    • Resistance (ohm) 1570
    • Format Cylindrical
    • Dimension 53x442mm
    • Homologations IEC
    • Weight (g) 2300
  • Fuse 36kV 53x442 back-up without striker 1A
    3018111.1.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 36000
    • Rated current In (A) 1
    • Pre-arcing I2t value (A2s) 0,63
    • Total I2t value (A2s) 1,8
    • Voltage of total I2t test 36000
    • Rated break.capacity I1 AC (A) 40000
    • Power loss (W) 13
    • Resistance (ohm) 9,57
    • Format Cylindrical
    • Dimension 53x442mm
    • Homologations IEC
    • Weight (g) 2300
  • Fuse 17,5kV 53x292 back-up without striker 2,5A
    3025511.2,5.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 17500
    • Rated current In (A) 2,5
    • Voltage of total I2t test 17500
    • Rated break.capacity I1 AC (A) 63000
    • Format Cylindrical
    • Dimension 53x292mm
    • Weight (g) 1640
  • Fuse 38,5kV TV 53x537 with striker 3,15A
    3033713.3,15.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 38500
    • Rated current In (A) 3,15
    • Pre-arcing I2t value (A2s) 17
    • Total I2t value (A2s) 48
    • Voltage of total I2t test 38500
    • Rated break.capacity I1 AC (A) 40000
    • Power loss (W) 29
    • Resistance (ohm) 2200
    • Format Cylindrical
    • Dimension 53x537mm
    • Homologations IEC
    • Weight (g) 2759
  • Fuse VT 36kV DIN 53x292 with striker 3,15A
    3038213.3,15.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 36000
    • Rated current In (A) 3,15
    • Pre-arcing I2t value (A2s) 17
    • Total I2t value (A2s) 48
    • Voltage of total I2t test 36000
    • Rated break.capacity I1 AC (A) 40000
    • Power loss (W) 26
    • Resistance (ohm) 1900
    • Format Cylindrical
    • Dimension 53x292mm
    • Homologations IEC
    • Weight (g) 1660
  • Fuse 7,4kV 24x142 TV protection 0,5A
    3038311.0,5.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 7200
    • Rated current In (A) 0,5
    • Pre-arcing I2t value (A2s) 0,1
    • Total I2t value (A2s) 0,9
    • Voltage of total I2t test 7200
    • Rated break.capacity I1 AC (A) 63000
    • Power loss (W) 1,9
    • Format BS
    • Dimension 24x142mm
    • Homologations IEC
    • Weight (g) 174
  • Fuse 15,5kV 39,6x327 TV ANSI 2E
    3043511.2E.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 15500
    • Rated current In (A) 2
    • E-Rating 2
    • Pre-arcing I2t value (A2s) 4
    • Total I2t value (A2s) 34
    • Voltage of total I2t test 15500
    • Rated break.capacity I1 AC (A) 70000
    • Power loss (W) 7,7
    • Format BS
    • Dimension 39,6x327mm
    • Homologations IEC
    • Weight (g) 1020
  • Fuse 24kV 39,6x327 M8 TV rough ceramic surface 1A
    3050711.1.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 36000
    • Rated current In (A) 1
    • Pre-arcing I2t value (A2s) 0,6
    • Total I2t value (A2s) 1,9
    • Voltage of total I2t test 24000
    • Rated break.capacity I1 AC (A) 63000
    • Power loss (W) 9
    • Format BS
    • Dimension 40x340mm
    • Homologations IEC
  • Fuse 40,5kV 537x53 back-up with striker 5A
    3034013.5.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 40500
    • Rated current In (A) 5
    • Pre-arcing I2t value (A2s) 40
    • Total I2t value (A2s) 125
    • Voltage of total I2t test 40500
    • Rated break.capacity I1 AC (A) 40000
    • Power loss (W) 47
    • Resistance (ohm) 1340
    • Format Cylindrical
    • Dimension 537x53mm
    • Homologations IEC
    • Weight (g) 2740
  • Fuse 15,5kV 39,6x327 TV ANSI 0,75E
    3043511.0,75E.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 15500
    • Rated current In (A) 0,75
    • E-Rating 0,75
    • Pre-arcing I2t value (A2s) 0,4
    • Total I2t value (A2s) 3,2
    • Voltage of total I2t test 15500
    • Rated break.capacity I1 AC (A) 70000
    • Power loss (W) 5
    • Format BS
    • Dimension 39,6x327mm
    • Homologations IEC
    • Weight (g) 1020
  • Fuse 17,5kV 53x367 back-up without striker 0,5A
    3017611.0,5.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 17500
    • Rated current In (A) 0,5
    • Pre-arcing I2t value (A2s) 1,6
    • Total I2t value (A2s) 5,9
    • Voltage of total I2t test 17500
    • Rated break.capacity I1 AC (A) 63000
    • Power loss (W) 8,1
    • Resistance (ohm) 29480
    • Format Cylindrical
    • Dimension 53x367mm
    • Homologations IEC
    • Weight (g) 2010
  • Fuse VT 36kV DIN 53x292 1A
    3038211.1.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 36000
    • Rated current In (A) 3,15
    • Pre-arcing I2t value (A2s) 0,63
    • Total I2t value (A2s) 1,8
    • Voltage of total I2t test 36000
    • Rated break.capacity I1 AC (A) 40000
    • Power loss (W) 13
    • Resistance (ohm) 9570
    • Format Cylindrical
    • Dimension 53x292mm
    • Homologations IEC
    • Weight (g) 1640
  • Fuse VT 36kV DIN 53x292 with striker 5A
    3038213.5.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 36000
    • Rated current In (A) 5
    • Pre-arcing I2t value (A2s) 40
    • Total I2t value (A2s) 125
    • Voltage of total I2t test 36000
    • Rated break.capacity I1 AC (A) 40000
    • Power loss (W) 23
    • Resistance (ohm) 650
    • Format Cylindrical
    • Dimension 53x292mm
    • Homologations IEC
    • Weight (g) 1680
  • Fuse 7,2kV 24x142 TV protection 3A
    3038311.3.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 7200
    • Rated current In (A) 3
    • Pre-arcing I2t value (A2s) 16,1
    • Total I2t value (A2s) 47,8
    • Voltage of total I2t test 7200
    • Rated break.capacity I1 AC (A) 63000
    • Power loss (W) 6,3
    • Format BS
    • Dimension 24x142mm
    • Homologations IEC
    • Weight (g) 170
  • Fuse 7,2kV 53x192 back-up with striker 5A
    3000213.5.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 7200
    • Rated current In (A) 5
    • Pre-arcing I2t value (A2s) 40
    • Total I2t value (A2s) 125
    • Voltage of total I2t test 7200
    • Rated break.capacity I1 AC (A) 63000
    • Power loss (W) 5
    • Resistance (ohm) 141
    • Format Cylindrical
    • Dimension 53x192mm
    • Homologations IEC
    • Weight (g) 1000
  • Fuse 7,2kV 24x195 TV protection ANSI 5E
    3037711.5E.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 7200
    • Rated current In (A) 5
    • E-Rating 5
    • Pre-arcing I2t value (A2s) 44
    • Total I2t value (A2s) 280
    • Voltage of total I2t test 7200
    • Rated break.capacity I1 AC (A) 80000
    • Power loss (W) 10
    • Format BS
    • Dimension 24x195mm
    • Homologations IEC
    • Weight (g) 220
  • Fuse 7,2kV 53x192 back-up with striker 2A
    3000213.2.0
    Manufacturer: SIBA

    • Class HH Back up
    • Rated Voltage Un AC (V) 7200
    • Rated current In (A) 2
    • Pre-arcing I2t value (A2s) 9,8
    • Total I2t value (A2s) 50
    • Voltage of total I2t test 7200
    • Rated break.capacity I1 AC (A) 63000
    • Min breaking current I3(A) 16
    • Power loss (W) 5
    • Resistance (ohm) 935
    • Format Cylindrical
    • Dimension 53x192mm
    • Homologations IEC
    • Weight (g) 1200
  • Fuse 24kV 53x442 TV without striker 2A
    3000611.2.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 24000
    • Rated current In (A) 2
    • Pre-arcing I2t value (A2s) 3,2
    • Total I2t value (A2s) 9,8
    • Voltage of total I2t test 24000
    • Rated break.capacity I1 AC (A) 63000
    • Min breaking current I3(A) 16
    • Power loss (W) 15,2
    • Resistance (ohm) 2,85
    • Format Cylindrical
    • Dimension 53x442mm
    • Homologations IEC
    • Weight (g) 2270
  • Fuse 17,5kV 53x367 back-up with striker 4A
    3017613.4.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 17500
    • Rated current In (A) 4
    • Pre-arcing I2t value (A2s) 31
    • Total I2t value (A2s) 90
    • Voltage of total I2t test 17500
    • Rated break.capacity I1 AC (A) 63000
    • Power loss (W) 16
    • Resistance (ohm) 690
    • Format Cylindrical
    • Dimension 53x367mm
    • Homologations IEC
    • Weight (g) 1980
  • Fuse VT 36kV 24x359 ANSI- IEEE 0,75E
    3038111.0,75E.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 36000
    • Rated current In (A) 0,75
    • E-Rating 0,75
    • Pre-arcing I2t value (A2s) 0,4
    • Total I2t value (A2s) 3,5
    • Voltage of total I2t test 36000
    • Rated break.capacity I1 AC (A) 25000
    • Power loss (W) 10,5
    • Format BS
    • Dimension 24x359mm
    • Homologations IEC
    • Weight (g) 800
  • Fuse 38,5kV TV DIN 53x537 without striker 2,5A
    3033711.2,5.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 38500
    • Rated current In (A) 2,5
    • Pre-arcing I2t value (A2s) 7,2
    • Total I2t value (A2s) 35
    • Voltage of total I2t test 38500
    • Rated break.capacity I1 AC (A) 40000
    • Power loss (W) 27
    • Resistance (ohm) 3050
    • Format Cylindrical
    • Dimension 53x537mm
    • Homologations IEC
    • Weight (g) 2760
  • Fuse 40,5kV 537x53 back-up with striker 2A
    3034013.2.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 40500
    • Rated current In (A) 2
    • Pre-arcing I2t value (A2s) 3,2
    • Total I2t value (A2s) 9,8
    • Voltage of total I2t test 40500
    • Rated break.capacity I1 AC (A) 40000
    • Power loss (W) 27
    • Resistance (ohm) 4800
    • Format Cylindrical
    • Dimension 537x53mm
    • Homologations IEC
    • Weight (g) 2740
  • Fuse VT 12kV 39,6x220 5A
    3037211.5.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 12000
    • Rated current In (A) 5
    • Pre-arcing I2t value (A2s) 40,9
    • Total I2t value (A2s) 120,7
    • Voltage of total I2t test 12000
    • Rated break.capacity I1 AC (A) 63000
    • Min breaking current I3(A) 40
    • Power loss (W) 16
    • Format BS
    • Dimension 40x220mm
    • Homologations IEC
    • Weight (g) 680
  • Fuse 7,2kV 24x195 TV protection ANSI 1E
    3037711.1E.0
    Manufacturer: SIBA

     
    • Class HH Back up
    • Rated Voltage Un AC (V) 7200
    • Rated current In (A) 1
    • E-Rating 1
    • Pre-arcing I2t value (A2s) 1
    • Total I2t value (A2s) 9
    • Voltage of total I2t test 7200
    • Rated break.capacity I1 AC (A) 80000
    • Power loss (W) 2,6
    • Format BS
    • Dimension 24x195mm
    • Homologations IEC
    • Weight (g) 220
Accept

This site uses cookies. By continuing to browse the site, you are agreeing to our use of cookies. More information